SECTION 5.5

You are at: ABOUT US > EMERGENCY > MARTELL POWER SYSTEMS

Martell Power Systems
AC/DC: AC/AC: Emergency lighting central battery systems

< PREVIOUS | NEXT >

Martell Power Systems

Print this page

The choice of Central Battery Emergency Lighting Systems.

The Martell range of central battery emergency lighting systems offer a number of advantages not only for use in medium to large installations that have the requirement for emergency lighting and signage but also where one or more of the following requirements exist:

 

Installations with a high luminaire mounting height, i.e. greater than 4 metres

Installations that require higher levels of illumination than just the legal minimum.

Installations that require central control for testing, monitoring or operation of the maintained lighting.

Installations requiring longer periods of emergency back-up than 3 hours.

Installations where it is desirable to utilise the normal mains luminaires under emergency or mains failure conditions.

Martell AC/DC Range 10 year design life Batteries

24v Designation
Load (Watts)
Cubicle 1 hour
Cubicle 3 hour
MLA 24/0.5/*
500
LP
LP
MLA 24/1.0/*
1000
LP
LP
MLA 24/1.5/*
1500
LP
LP
MLA 24/2.00/*
2000
A+B
A+B
 

50v Designation
Load (Watts)
Cubicle 1 hour
Cubicle 3 hour
MLA 50/0.5/*
500
LP
LP
MLA 50/1.0/*
1000
LP
LP
MLA 50/1.5/*
1500
A+B
A+B
MLA 50/2.0/*
2000
A+B
A+C
MLA 50/2.5/*
2500
B+B
B+E
MLA 50/3.0/*
3000
B+B
B+E
MLA 50/3.5/*
3500
B+C
B+E
MLA 50/4.0/*
4000
B+C
B+E
MLA 50/4.5/*
4500
B+C
B+E
MLA 50/5.0/*
5000
B+C
B+E
MLA 50/6.0/*
6000
B+C
B+2E
MLA 50/7.0/*
7000
C+E
C+2E
MLA 50/8.0/*
8000
C+E
C+2E
MLA 50/9.0/*
9000
C+E
C+2E
MLA 50/10.0/*
10000
C+E
C+2E
MLA 50/11.0/*
11000
C+E
C+2E
 
110v Designation
Load (Watts)
Cubicle 1 hour
Cubicle 3 hour
MLA 110/0.5/*
500
LP
LP
MLA 110/1.0/*
1000
LP
LP
MLA 110/1.5/*
1500
A+B
A+B
MLA 110/2.00/*
2000
A+B
A+C
MLA 110/2.5/*
2500
B+B
B+E
MLA 110/3.0/*
3000
B+B
B+E
MLA 110/3.5/*
3500
B+C
B+E
MLA 110/4.0/*
4000
B+C
B+E
MLA 110/4.5/*
4500
B+C
B+E
MLA 110/5.0/*
5000
B+C
B+E
MLA 110/6.0/*
6000
B+C
B+2E
MLA 110/7.0/*
7000
C+E
C+2E
MLA 110/8.0/*
8000
C+E
C+2E
MLA 110/9.0/*
9000
C+E
C+2E
MLA 110/10.0/*
10000
C+E
C+2E
MLA 110/11.0/*
11000
C+E
C+2E

* FOR FULL EQUIPMENT DESIGNATION, SPECIFY DURATION (1 OR 3 HOURS) / MODE (NM, M OR F), e.g. MLA/110/3/NM3


Back to top

System Sizing.
AC systems

The system size is determined by a combination of the size of the load (W) and the duration required under mains fail conditions, e.g. a maintained AC/DC system required to run the following luminaires for 3 hours would be sized thus:

1. 20 x 20W tungsten lamps

2. 40 x 18 W T8 lamps

3. 10 x 8 W Exit box luminaires.

 
Load
(VA)
(W)
1. Tungsten load
400
400
2. Long lamp conversion
1011
920
3. 8W exit luminaires
105
95
Total
1516VA
1415W
The system is sized to VA and the battery the W figure.

Martell Power Range

Fitzgerald Lighting has long been a significant supplier of central battery emergency lighting systems supplying both DC systems and static inverter systems from 100 Watts to 100 kWatts, single and three phase input/output.

Martell AC/DC
System Specification

Electrical

Input Voltage 230 Vac, 110 Vac
- Frequency 50Hz, 60Hz
- Phases Single or Three phase
Output Voltage 230 Vac, 110 Vac Maintained
- Options 24, 50 or 110 Vdc Non Maintained
- Frequency 50Hz, 60Hz
- Phases Single or Three phase
- Category NM - Non-maintained
- - M - Maintained or permanent
- - F - Floating
 

Charger

Capable of charging the battery to be able to provide at least 80% of rated duration, with the rated load applied, within 12 hours. 100% of capacity available within 24 hours. Automatic temperature compensation of battery charge voltage.

Enclosures

Fully welded construction with lockable, hinged front door(s).

Top cable entry facilitated through un-drilled gland plate.

Constructed of 1.5mm steel sheet cladding, 2mm sheet steel door with tubular stiffening rails and a base mounting plate with folded edges constructed from 2.5mm zintec.

Standard IP rating; IP21

Standard colour finish RAL7032 textured.

Martell AC/AC Range
of Emergency Lighting Static Inverters

The Martell inverter is specifically designed for emergency lighting. It is controlled by a micro processor and is very reliable, quiet and efficient in operation.

Incorporating MustStart™ technology Martell inverters are guaranteed to start any lighting load within its rating from "cold". The addition of PowerFlow™ circuitry allows normal operation to resume even after the clearance of a complete short circuit on the inverter output.

These technologies are incorporated to ensure the availability of emergency power under the most demanding circumstances and to give users complete piece of mind.

 

Fascia panel

 Fascia panel

Martell Range of
Static Inverters

Illustrated below is the standard range of single phase input/output inverter systems utilising 10 year design life sealed recombination lead acid batteries.

Please contact us for information regarding 3 phase operation and alternative battery types.

 

Single phase Input/Output**
Designation
Unit KVA
Unit KW
1 hour Cubicles
3 hour Cubicles
FAC/0.5/*
0.6
0.5
LP
LP
FAC/1.0/*
1.0
0.9
LP
LP
FAC/1.5/*
2.0
1.7
A+B
A+C
FAC/2.0/*
2.5
2.1
A+B
A+B
FAC/2.5/*
3.0
2.6
2B
B+C
FAC/3.0/*
4.0
3.4
2B
B+E
FAC/4.0/*
5.0
4.3
2B
B+E
FAC/5.0/*
6.0
5.1
B+C
B+E
FAC/6.0/*
7.0
6.1
C+E
C+2E
FAC/7.0/*
8.5
7.2
C+E
C+2E
FAC/9.0/*
10.5
8.5
D6+E
D6+2E
FAC/11.0/*
12.5
10.6
D8+E
D8+2E
FAC/13.0/*
15.0
12.8
D8+2E
D8+3E
FAC/14.0/*
16.5
14.0
D8+2E
D8+3E
FAC/17.0/*
20.0
17.0
D8+2E
D8+4E
FAC/19.0/*
22.0
18.7
D8+2E
D8+4E
FAC/20.0/*
24.0
20.4
2D6+2E
2D6+4E
FAC/22.0/*
26.0
22.1
2D8+2E
2D8+4E
 

* Specify emergency duration i.e. 1 or 3 hour

** 3 phase input/output versions are available

 
Back to top