SECTION 4.43

You are at: ABOUT US > FIRE DETECTION > MI-DISO ISOLATOR MODULES

MI-DISO Isolator Modules

< PREVIOUS | NEXT >

 

MI-DISO Isolator Modules
MI-DISO Isolator Modules rail mounting
One year guarantee symbol
3 year guarantee symbol
Enhanced 3 year warranty applicable when commissioned by Fitzgerald Service.
 

Print this page

Features

DIN rail mounting option.

Surface mounting option.

Plug in connectors.

Tri-colour LED status indication.

Address selector switches visible in 2 planes.

LED status visible in 2 planes.

Approved to GEA GEI 1-082 and CEA GEI 1-084.

 

The loop isolator module is used on intelligent fire alarm control panels to protect the system against wire-to-wire short circuits on the analogue addressable loop wiring.

The fault isolator modules should be placed between groups of sensors on the loop wiring to protect the loop if a short circuit fault occurs. If a short circuit fault occurs, the two isolators located either side of the short circuit fault will automatically sense the voltage drop, open their switches and remove the devices from the rest of the loop. If the line voltage then rises above a fixed threshold, indicating that the short circuit fault is removed, then the isolator module will automatically restore the power to the isolated group of devices.

The MI-DISO isolator uses a unique mechanical design allowing each module to be mounted either in a wall box or on a DIN rail. Irrespective of the mounting method chosen, the address switch is both visible and accessible for selection.

To help engineers in the maintenance and fault finding process, both the LEDs and the address switches can be viewed without having to remove the cover of the mounting box. The LEDs, being multi colour, provide diagnostic information regarding the status of the isolator.

Mechanical

Dimensions 93 x 94 x 23 mm (H x W x D)
Weight 62gr.
Operating temperature -20 to +60°C
Humidity 0 to 95% maximum non-condensing

Dimensions

Dimensions diagram

Exploded view

Electrical

Operating Voltage 15 - 30 Vdc
Standby current 200ľA at 24 Vdc maximum
Fault detection delay 100 to 400 mS
On resistance 0.065 at 15 Vdc
Terminal Wire 2.5 mm2 maximum

Wiring Details

 

Wiring Details

 

Part Numbers

F850817 Addressable Isolator Module. (MI-DISO)
Accessories
F850819 Surface mounting box. (M200E-SMB)
F850719 DIN rail mounting clip. (M200E-DIN)