Fitzgerald logolink to home page

Fitzgerald banner graphic

about us link

link to news

link to contact page

link to contents index

link to gallery

link to FAQ

SECTION 4.42

You are at: ABOUT US > FIRE DETECTION > ADDRESSABLE CONTROL OUTPUT MODULE

MI-DCMO Addressable Control Output Module

< PREVIOUS | NEXT >

 

MI-DCMO Addressable Control Output Module
MI-DCMO Addressable Control Output Module rail mounting
One year guarantee symbol
3 year guarantee symbol
Enhanced 3 year warranty applicable when commissioned by Fitzgerald Service.
 

Print this page

Features

DIN rail mounting option.

Surface mounting option.

Tri-colour LED status indication.

Built-in Short Circuit Isolators.

Visible Address selector switches.

LED status visible in 2 planes.

Plug in connectors.

Approved to GEA GEI 1-082 and CEA GEI 1-084.

 

The MI-DCMO control output module is used to provide either a single alarm circuit or Form C relay.

The MI-DCMO can be used to operate dry contacts for door holders, air handling unit shut down or other similar functions. Optionally the module can be used to supervise wiring to the ouput load providing monitoring of the external load voltage or power supply. If the monitored voltage falls below threshold then a fault condition will be indicated.

Each MI-DCMO uses one of the ninety-nine possible module addresses available on a loop. It responds to regular polling from the conrtol panel indicated by a pulsing LED every successful communication. On command from the control panel the MI-DCMO will disconnect the supervision and connect the external power supply across the load. The disconnection of the supervision provides a positive indication to the control panel that the relay is activated. The MI-DCMO has a built-in isolator which may be switched out if required.

The MI-DCMO uses a unique mechanical design allowing each module to be mounted either in a wall box (M200-SMB) or on a DIN rail (using M200- DIN). Irrespective of the mounting method chosen, the address switch is both visible and accessible for selection.

To help engineers in the maintenance and fault finding process, both the LEDs and the address switches can be viewed without having to remove the cover of the mounting box. The LEDs, being multi colour, provide diagnostic information regarding the status of the output. For ease of installation, testing and maintenance, the field wiring terminals are of a plug in design.

Mechanical

Dimensions 93 x 94 x 23 mm (H x W x D)
Weight 100gr.
Operating temperature -20 to +60°C
Humidity 0 to 95% maximum non-condensing

Dimensions

Exploded view

Electrical

Operating Voltage 15 - 32 Vdc
Standby current No comms 340ľA at 24 Vdc maximum
1 comms every 5 seconds with LED blink 510ľA at 24 Vdc maximum
Terminal Wire 2.5 mm2 maximum
Relay Form C Unsupervised 2A at 30 Vdc, resistive load
Supervised 1.5A at 30 Vdc, resistive load

Connection Details

Supervised and
Unsupervised output

Connection details diagram 1

Connection details diagram 2

Part Numbers

F850813 Single channel addressable output module. (MI-DCMO)
Accessories
F850819 Surface mounting box. (M200E-SMB)
F850719 DIN rail mounting clip. (M200E-DIN)
  Back to top