Features

Dual inputs.

Single relay output.

DIN rail mounting option.

Surface mounting option.

Tri-colour LED status indication.

Built-in short circuit isolators.

Visible address selector switches.

LED status visible in 2 planes.

Plug in connectors.

Approved to GEA GEI 1-082 and CEA GEI 1-084.

 

The MI-D2ICMO dual input/single output modules provide a dual input circuit from external devices and a single relay control output circuit.

Each input is continuously monitored for normal, open circuit and alarm conditions. Any change in the status of the input circuits are communicated to the panel where the appropriate actions may be undertaken. A single pole volt free changeover relay is available for control of external devices or circuits.

The MI-D2ICMO requires three addresses per unit of the ninety-nine possible module addresses available on a loop. It responds to regular polling from the control panel indicated by a pulsing LED every successful communication.

The MI-D2ICMO uses a unique mechanical design allowing each module to be mounted either in a wall box (M200E-SMB) or on a DIN rail (using M200E-DIN). Irrespective of the mounting method chosen, the address switch is both visible and accessible for selection.

To help engineers in the maintenance and fault finding process, both the LEDs and the address switches can be viewed without having to remove the cover of the mounting box. The LEDs, being multi colour, provide diagnostic information regarding the status of the output. For ease of installation, testing and maintenance, the field wiring terminals are of a plug in design.

Mechanical

Dimensions 93 x 94 x 23 mm (H x W x D)
Weight 100gr.
Operating temperature -20 to +60°C
Humidity 0 to 95% maximum non-condensing

Dimensions

Dimensions diagram

Exploded view

Electrical

Operating Voltage 15 - 32 Vdc
Standby current No comms 340ľA at 24 Vdc maximum
1 comms every 5 seconds with LED blink 660ľA at 24 Vdc maximum
Relay contacts rating 2A at 30 Vdc, resistive load
Terminal Wire 2.5 mm2 maximum

Connection Details

Connection Details diagram

Part Numbers

F850902 Dual channel input/Single channel output addressable module. (MI-D2ICMO)