Features

Dual thermistors.

Rate-of-rise fixed temperature and high fixed temperature models.

Common base for optical, ionisation and thermal sensors.

Addressable-analogue communication.

Stable communication technique with noise immunity.

Low stand-by current.

Rotary decade 01 to 99 address switches.

Remote LED output as standard.

Dual LED design provides 360° viewing angle.

Visible LED's blink every time the detector is addressed (optional), and illuminate steady on alarm.

Built-in functional test switch activated by external magnet.

Optional relay, isolator, or sounder bases.

 

Our range of intelligent thermal detectors are used with the ZX & DX series intelligent multi protocol fire alarm control panels to measure thermal levels caused by a fire and report the analogue level of the thermal measurement to the control panel.

The use of analogue information provides significant benefits to the end user, installer and serviceman in ways which are not possible with a conventional type system. Since this detector is also addressable, it will help to quickly locate a fire during its early stages.

The MI-FHSE and MI-HTSE are fixed temperature analogue addressable sensors employing low mass thermistors and microprocessor technology for fast response and linear temperature sensing. Their linear response allows these sensors to be used to signal temperatures over the range of 58°C (Class A1S) to 78°C (Class BS).

The MI-RHSE uses the same thermistor and microprocessor technology to provide an alarm when the rate of rise in temperature exceeds 10°C/minute (typical) or if the temperature exceeds a threshold of 58°C (Response Class A1R). All of the thermal detectors have two integral alarm LEDs which provide local visual indication of the sensor status. These LED's provide a dual function. In the event on an alarm, they are switched ON continuously, and can also be programmed to either blink when polled by the panel or remain off during normal conditions.

Mechanical

Dimensions 51 mm (installed in B501)
Weight 170g
Operating temperature -10°C to +60°C
Relative humidity 10% to 93% non-condensing
Compatible bases B501, B524IEFT, B524RLY

Dimensions

Dimensions

Electrical

Voltage +15 to +32Vdc
Current consumption Stand by current - 200 ľA maximum LED current - 7 mA @ 24 Vdc ("ON") Alarm current (LED on) - 7mA maximum
Terminals SEMS screws with clamping plates for up to 2.5 mm2 (13 AWG) wire

Part Numbers

F850874 Rate of rise heat sensor. Class A1R. (LPCB REF:199n/04) (MI-RHSE)
F850859 Fixed temperature (135%, 57°C) sensor, Class A1S. (LPCB REF:199n/03) (MI-FHSE)
F850860 Fixed high temperature sensor (78°C, 172°F), Class BS. (LPCB REF: 199n/05) (MI-HTSE)
Other accessories
F850726 Surface mounting kit provides for entry of surface wiring conduit. For use with B501 base only. (SMK400)
F850727 Recess mounting kit. For use with B501 base only. (RMK400)
F850806 Detector mounting base. (B501)
F850877 Detector mounting base fitted with loop isolator. (B501IEFT)

Note

1) For Class A1S & A1R sensors the maximum ambient temperature should not exceed 45°C to minimise occurance of unwanted alarm conditions.

2) For Class BS sensors the maximum ambient sensors should not exceed 68°C to minimise occurance of unwanted alarm conditions.

 

Wiring

Wiring diagram