| Operating
Voltage |
230Vac
(+10%, -15%) 50-60 Hz |
| PSU
Rating |
DX2e-40M(F) |
24
Vdc 4A |
| DX2e-40MP(F) |
24
Vdc 4A |
| DX2e-40L(F) |
24
Vdc 4A |
| DX2e-40LP(F) |
24
Vdc 4A |
| Stand-by
Batteries |
DX2e-40M(F) |
2
x 7Ahr or 2 x 12AHr |
| DX2e-40MP(F) |
2
x 7Ahr or 2 x 12AHr |
| DX2e-40L(F) |
2
x 12AHr or 2 x 17AHr |
| DX2e-40LP(F) |
2
x 12AHr or 2 x 17AHr |
| Auxiliary
output* |
+24
Vdc 250mA fused |
| Loop
Capacity** |
2
Loops, 500mA per loop |
| 126
devices per loop, Apollo Protocols |
| 126
devices per loop, Hochiki ESP Protocol |
| 198
devices per loop, Morley-IAS Protocol |
| 198
devices per loop, System Sensor Protocol |
| Output
Relays |
Fire
relay - Single pole changeover 30Vdc 1A |
| Fault
relay - Single pole changeover 30Vdc 1A |
| Aux
relay - Programmable single pole changeover 30Vdc 1A |
| Onboard
Inputs |
Keyswitch
- programmable for select functions |
| Input
#1 - programmable (monitored) for select functions |
| Input
#2 - programmable (monitored) for select functions |
| Data
Ports |
F850876 |
1
x RS 485 (Repeater connections) |
| F850951 |
1
x RS232 (PC Programming) |
| Sounder
Circuits |
2
output circuits, 1A available across both circuits* |
| Note |
*
Maximum available current will be dependent on full control panel
loading. |
| **