Fitzgerald logolink to home page

Fitzgerald banner graphic

about us link

link to news

link to contact page

link to contents index

link to gallery

link to FAQ

SECTION 4.5, 4.6

You are at: ABOUT US > FIRE DETECTION > CONVENTIONAL CONTROL PANELS (4 WIRE)

Conventional Control Panels (4 wire)

 

Conventional Control Panel (4 wire)
One year guarantee symbol
3 year guarantee symbol
Enhanced 3 year warranty applicable when commissioned by Fitzgerald Service.
 

Print this page

Features

Simple, user friendly design

Simple to install

Intuitive to use

2, 4 or 8 Zones

Walk test

Enhanced feature set

Multilingual text inserts

Designed to comply with EN54 part 2 and part 4.

 

The Martell Horizon series of conventional control panels has been developed to provide a simple and reliable solution to the demands of today's fire detection solutions.

The range has been designed with both installer and end users requirements in mind.

For installers, the range offers an out of the box and on the wall solution. A combination of quick installation, an enhanced feature set and advanced programming allows installers to quickly and simply meet the demands of end user. Equipped with configurable class change inputs, coincidence detection, programmable delays to allow alarm verification and the facility to interface to larger house alarm systems.

For end users, clear visible indications, easy to operate functions and a big red key to activate the control buttons, make for simple and unambiguous operation.

Engineered and built to the same high standard as all Fitzgerald products, the Martell Horizon system forms an essential part of any fire alarm solution.

The series of conventional control panels has been designed for use in small to medium commercial environments. It is specially suitable for Garages, Retail Units, Shops, Restaurants, Doctor's surgeries, Public Offices, Nursery Schools.

Mechanical

Dimensions 318 x 356 x 96 mm (h x w x d)

Weight 2 Kg (approx, no batteries fitted)

Construction Fire retardant, ABS plastic moulded enclosure, sealed to IP30

Cable entry 18 x 20mm knockouts in top of enclosure 25 x 50 mm knockout in rear of enclosure

Operating Temperature +5°C to +35°C

Relative Humidity 5% to 95% non condensing

Electrical

Operating voltage

230 Vac 50/60 Hz (±15%)

Internal Power supply

Output voltage: +18.5 to +28.5 Vdc

Output Current: 1.8 Amps maximum

Maximum Alarm load

1 Amp

Standby Batteries

Minimum capacity: 2 x 12 V 2.8Ah

Maximum capacity: 2 x 12 V 7 Ah

Standby Battery type

Sealed lead acid

Detection circuits

2, 4 or 8 detection circuits

2 mA per circuit (typically >20 detectors)

Approved detectors

Apollo Series 60 wide voltage, Series 65 & Orbis

Morley-IAS Horizon HRZ Series
System Sensor ECO1000, Series 300 & Vision

Digital Inputs

2 configurable inputs (Class Change, Alert, Evacuate, Reset)

Digital Input trigger

Extended Closing contact

External outputs

Sounder outputs: 2 monitored outputs

0.5 Amps per circuit
Auxiliary output: +18.5 to +28.5 Vdc, 0.5 Amp. (max)

Optional Relay card

1 x Fire relay (changeover contacts rating 30Vdc, 1 Amp)

1 x Fault relay (changeover contacts rating 30Vdc, 1 Amp)

Max wire gauge for terminals

2.0 mm2

Control Panel

Control Panel diagram

Ordering
ORDERING REF
TYPE
F850768
HORIZON HRZ 2 ZONE FIRE ALARM CONTROL PANEL (HRZ 2 ZONE)
F850770
HORIZON HRZ 4 ZONE FIRE ALARM CONTROL PANEL (HRZ 4 ZONE)
F850772
HORIZON HRZ 8 ZONE FIRE ALARM CONTROL PANEL (HRZ 8 ZONE)
F850891
HORIZON RELAY KIT (FIRE & FAULT RELAYS) (HRZ RELAY)