SECTION
0.6
|
You are at: ABOUT US > EXODUS CONTROLS > CONTROL GEAR |
Control Gear |
CLICK
DIAGRAM TO ENLARGE AS A POP-UP WINDOW
|
|
|||||||||||||||||||||||||||||||||
|
Exodus Marshalling Boxes E016603 and E016604 can be used with fixed output or DSI dimmable control gear. To order lighting with DSI dimmable gear, order as Luminaire code.../DTD. Exodus Marshalling Box E016605 is for use with Switch-dim fittings only. To order the appropriately wired fittings, order as Luminaire code.../SD. Exodus Marshalling Boxes E016600 and E016620 must be used with DSI dimmable control gear only. DSI (Digital Serial Interface) is our preferred control protocol for lighting. Though DSI operates at 12v it should always be wired in mains rated cable or flex. However, there is no need for DSI wires to be screened or segregated in any special way from power or other cables. A comprehensive range of DSI operated HF control gear for linear and compact fluorescent is available. In addition, there is a wide range of DSI control gear for incandescent lamps, LEDs and other loads, as in the above diagram. |
|||||||||||||||||||||||||||||||||||
|
|||||||||||||||||||||||||||||||||||
|